XM31-918-HP - 10124552
Batteries
 
 

Alarms
 

Battery
 

Batteries
Battery String Voltage 40.92 V
Estimated Runtime At least 12 hours
Battery Life Remaining Over five years
Battery Balancing Balanced
Balancing String String A
Battery System Configuration 1 string of 3 batteries
Battery Temperature 19 °C
66 °F
  1 2 3 Balancing
String A 13.72 V 13.67 V 13.68 V Normal
Battery Charging
Charger Mode Float
Current Charger Mode Time 120 min
Charger Current 0.05 A
Charger Current Limit 10.50 A
Charger Enable Yes
Configuration
Technician ID 0
24 Hour Battery Refresh No
Battery Model 4.0HP
Accept Voltage 2.35 V/cell
Float Voltage 2.25 V/cell
Refresh Voltage 2.45 V/cell
Battery Capacity 114 Ah
Temperature Compensation 4.00 mV/cell/°C
HP Battery Rest Mode Yes
Battery String Detect Auto
Number of Battery Strings 1
Heater Mat Installed No
Conductance
Last Conductance Measurement  
  Last Adjusted Conductance Measurement Manufactured Date
String A Battery 1 0 S(℧)  
String A Battery 2 0 S(℧)  
String A Battery 3 0 S(℧)  

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.